RFQ - 12.5-Ton Gas/Electric Rooftop Unit Package
Subject: RFQ - 12.5-Ton Gas/Electric Rooftop Unit PackageSolicitation Number: W911S226U3282Notice Type: SOLICITNAICS: 333415Set-Aside: Total Small BusinessNotice Published: 05-20-26Response Due: 05-28-26Agency: Department of the ArmyOffice: W6QM MICC-FT DRUMContact: Daniel Goldberg This email address is being protected from spambots. You need JavaScript enabled to view it. Ph: (301) 619-9146Office Address: FORT DRUM, NY 13602-5220Place of Performance: 9250 Amber Dr Frederick MD, 21702 21702Related Notices:
Click for official SAM (FBO) notice, additional information, and accompanying attachments
Amended to change NAICS code. This requirement is for a complete, like-for-like replacement of an existing commercial rooftop unit, or RTU. The required equipment package must meet or exceed the following specifications. The base unit must be one 12.5-Ton Gas Heat and Electric Cooling Rooftop Unit with a 208-volt, 3-phase power supply. The unit must have single circuit, two-stage cooling with a minimum 10.8 EER or 15.0 IEER, and two-stage medium gas heat with a first stage of 180 MBH input and a second stage of 224 MBH input. It must also feature a high-static direct-drive vane axial fan, such as a Carrier EcoBlue or equivalent, and use a modern, low GWP refrigerant like R-454b. The package must also include the following compatible accessories: one Vertical Economizer with a controller, one Enthalpy sensor and harness for the economizer, and one standalone, two-stage programmable thermostat.