Y1DA--630A4-26-401 MRI AHU Modification
Subject: Y1DA--630A4-26-401 MRI AHU ModificationSolicitation Number: 36C24226R0060Notice Type: SOLICITNAICS: 236220Notice Published: 06-30-26Response Due: 07-09-26Agency: Department of Veterans AffairsOffice: VETERANS AFFAIRS, DEPARTMENT OFContact: Kimberly A Gomez (Contractor), Contract Specialist This email address is being protected from spambots. You need JavaScript enabled to view it.Office Address: ALBANY, NY 12208Related Notices:
Click for official SAM (FBO) notice, additional information, and accompanying attachments
36C24226R0060 Amendment 2 630A4-26-401 MRI AHU Modification Please verify if you are looking for any redundancy in the chiller? Do you want N+1 for the chiller? Or redundant circuits? VA response: We have the in house as a backup for the summer. Please verify if we need to include survey/SUE/geotechnical/full civil for the outside pad location for option 1 and option 2? VA response: Yes, the contractor will need to do a survey. Do you have, or can you provide any as-builts for current utilities in the hallway ceiling outside the MRI room? VA response: No As-builts they seen the space, so we are good from the point. Can you provide an extension on the bid due date? VA response: Yes. Extended to Jul 9, 2026. Can you please provide an update for Phase II submission requirements for proposal submission? Nothing is in the documents: VA response: Please see the attached.