Sewage Ejector and Line Assessment
Subject: Sewage Ejector and Line AssessmentSolicitation Number: W912BV26QA069Notice Type: SOLICITNAICS: 237110Notice Published: 09-28-26Response Due: 10-28-26Agency: Department of the ArmyOffice: W076 ENDIST TULSAContact: CALEB DAVIS This email address is being protected from spambots. You need JavaScript enabled to view it. Ph: (918) 669-0237Office Address: TULSA, OK 74137-4290Related Notices:
Click for official SAM (FBO) notice, additional information, and accompanying attachments
This scope of work requires the contractor to locate, inspect, and modify an unmapped 700 to 800 foot concrete-encased four inch cast iron sewer line and its associated distribution box, with mandatory Government presence during all site inspections. Key tasks include installing concrete-encased Schedule 40 PVC double-Y clean-outs every 300 feet, exposing and inspecting the distribution box and its 2009 leach field connections, and extending the box cover using a riser and structural cover rated for three ton vehicle traffic protected by four concrete-encased steel safety-yellow bollards. All physical, material, and dimensional adjustments must be documented as Red Line As-Builts on the reference drawing, and any recommended corrective actions for the lateral lines must be delivered via a detailed findings report with comprehensive labor and material cost estimates.